Flood Risk Assessment, Flood Zone 3a Garden Outbuilding, Twickenham

A single-storey outbuilding providing ancillary accommodation in the rear garden of a house in Cole Park Road, Twickenham, near the River Crane. The site was in Flood Zone 2 when Air & Flood Consultants wrote the first FRA in February 2026 and in Flood Zone 3 by October 2026, after the Environment Agency adopted its 2024 River Crane model. The revised FRA takes a design flood level of 6.81 mAOD from the Environment Agency's Product 6 data, sets the floor at 7.11 mAOD with resistance to 7.41 mAOD, and provides 11.5 m³ of floodplain storage against 10.2 m³ displaced by removing a summer house and lowering part of the garden. The application was submitted on 19 October 2026 and is yet to be registered.

Air & Flood Consultants drawing of Environment Agency LiDAR ground levels at a garden outbuilding in Cole Park Road, Twickenham: the site boundary, the proposed outbuilding and patio, the summer house to be removed, the garden lowering area to 6.51 mAOD and the Flood Zone 3 and design flood level contours.

Flood Risk Assessment for a Garden Outbuilding in Flood Zone 3a, Cole Park Road, Twickenham
Location: Cole Park Road, Twickenham, London Borough of Richmond upon Thames | Services: Flood Risk Assessment; Floodplain Compensation; Flood Warning and Evacuation

The Proposal
The proposal is a single-storey timber-clad outbuilding in the rear garden of a house in Cole Park Road, Twickenham, providing ancillary accommodation to the main house: a bedroom, a shower room and a sitting room with a kitchenette. It measures 8.85 x 5.35 m (47.5 m²) and 3.84 m high, on a suspended floor, with a patio. The existing summer house (23.4 m²) and its ground-bearing slab are to be removed.

A Flood Zone That Changed Between Two Versions of the Report
Air & Flood Consultants wrote the first FRA for an earlier ancillary accommodation scheme on the site in February 2026. The Flood Map for Planning then placed the site in Flood Zone 2, and that report left the floor level pending Environment Agency data. When the scheme was redrawn in October 2026, the map was generated again for the same point and showed Flood Zone 3: the Environment Agency had adopted its River Crane model (AECOM, 2024) in between. The first report was superseded. The revised FRA added a check of Flood Zone 3a against the functional floodplain, floodplain compensation and a flood warning and evacuation plan, none of which the first report had needed. The site is in Flood Zone 3a, not 3b: the defended 5% AEP (1 in 20-year) outline stays within the River Crane channel, about 46 m from the site.

The Design Flood Level
The Environment Agency's Hertfordshire and North London office no longer issues a Product 4 for this river. It supplied the River Crane model results as Product 6 data under a conditional licence (EIR2026/09011), and stated that finished floor levels should be set at the 1% AEP flood level with climate change plus 300 mm. The data show the site dry in the defended 1% AEP event and in that event with the 17% central (2080s) climate change allowance. The highest defended level modelled next to the site is 6.81 mAOD, in the 1% AEP event with the 54% upper end allowance at the Cole Park Road frontage, and that level was adopted as the design flood level. The outbuilding floor is set at 7.11 mAOD, 300 mm above it in line with paragraph 16.69 of the Richmond Local Plan, with flood-resistant construction and all services carried to at least 7.41 mAOD.

The Survey Datum
The levels on the architect's drawings first appeared to sit about 3 m above the flood level. A comparison with Environment Agency LiDAR showed that the topographical survey had used an arbitrary local datum about 3.32 m above Ordnance Datum, so the drawn floor was about 0.2 m above the design flood level, not 3 m. The architect reissued the drawings in mAOD with the floor raised by 110 mm to 7.11 mAOD.

Floodplain Storage
Storage was calculated cell by cell from Environment Agency LiDAR, as the depth of the design flood over each part of the footprint, with no credit taken for the void beneath the suspended floor. The outbuilding displaces 10.2 m³ below 6.81 mAOD, at depths of up to 0.30 m. Removing the summer house and its slab restores 6.3 m³, and lowering garden ground above 6.51 mAOD to that level over 111 m² provides a further 5.3 m³, so 11.5 m³ is provided against 10.2 m³ displaced. Level for level, the two lower 0.1 m slices are met; the two upper slices, from 6.61 to 6.81 mAOD, are 4.0 m³ short, because the garden lies almost entirely below 6.61 mAOD and holds no ground at those levels to lower. No ground is to be raised anywhere in the garden.

Sequential Test and Evacuation
The outbuilding is to remain ancillary to the main house, so it is householder development, exempt from the Sequential Test under NPPF policy F5(2)(c), with the Exception Test disapplied by policy F6(2). The FRA sets out registration with the Environment Agency's flood warning service for the River Crane at Twickenham and early evacuation along Cole Park Road to London Road, 202 m away and outside Flood Zones 2 and 3. Roof runoff is to be managed at source, with a water butt overflowing to a rain garden or permeable surfacing, and a non-return valve is to be fitted on the foul connection.

Outcome
The revised FRA was issued in October 2026 and the application was submitted to the London Borough of Richmond upon Thames on 19 October 2026. It is yet to be registered, and its reference is to be added when it appears.